OHA Drinking Water Services
OHA Drinking Water Services
Contact Report Details

PWS ID: OR41 91589
PWS Name: MCKEE BRIDGE STORE/RESTAURANT
 
Who Was Contacted and Phone: Preston Shreves ( ) 899-1101 ext. or 899-1828 (home)
Contact Date: 01/02/2007
Contacted By: HOUGH, DANIEL (JACKSON COUNTY)
Contact Method/Location: Office
 
Assistance Type: WATER QUALITY ALERT RESPONSE
Reasons: Coliform
N/A
 
Details: SUMMARY: One of two routine samples collected on 01/02/06 tested positive for Total Coliform. DETAILS: 01/03/07- The well passed and the kitchen sink failed (again). Preston thinks that the problem might be the housing of the charcoal filter on the kitchen sink line. Although the charcoal element was removed, the housing is still in place. He will collect a special sample at the tap immediately prior to the housing. If this sample is positive he will replace the kitchen sink fixture.
01/08/07- Two special samples failed (pre-charcoal filter housing and kitchen sink). I spoke with Preston. He turned in a sample collected at the well again today. He said that he is going to work his way down the line testing every tap along the way. I talked to him about the possibility of a break in the line somewhere. He said that there is no system pressure loss. Preston is very concerned and has chosen to take the extra precaution of using only bottled water.
01/09/07- The sample collected at the well tested positive for Total Coliform. I called and left a message for Preston explaining that there is probably low level Total Coliform present and that he is going to have to chlorinate again.
01/19/07- One special sample collected at the kitchen passed. ACTION NEEDED: Five routine samples need to be collected in the month of February.


More information for this water system: SDWIS ID 942
System Info  ::  Report for Lenders  ::  Alerts  ::  Violations  ::  Compliance & Enforcement  ::  Contacts & Advisories  ::  Site Visits  ::  Public Notice
Coliform Summary  ::  Coliform Results  ::  Coliform Schedules  ::  LT2  ::  GW/GWUDI Source Details  ::  Plan Review  ::  Annual Fee
Chemical Summary  ::  Chemical Results  ::  Chemical Schedules  ::  Chemical Schedule Summary  ::  Arsenic RAA  ::  Cyanotoxins  ::  PFAS
Lead & Copper  ::  DBP Sample Sites  ::  FANLs  ::  MRDL  ::  GWR 4-Log  ::  Turbidity  ::  SWTR  ::  LRAA  ::  DW Source Protection
New! Visit our new Drinking Water Source Protection page.

Information for all water systems:
Water System Inventory  ::  Water System Surveys  ::  Outstanding Performers  ::  Treatment Plant Inspections  ::  Treatment  ::  Plan Reviews
Alerts  ::  Violations  ::  Compliance & Enforcement  ::  Deficiencies  ::  System Scores  ::  Exceedances  ::  Public Notices  ::  Service Lines
Water Advisories  ::  Contact Reports  ::  Cyanotoxins  ::  PFAS  ::  Post-wildfire VOCs  ::  Fluoride  ::  Certification List  ::  DW Source Protection

Introduction  ::  Data Search Options  ::  Water System Search  ::  DWS Home  ::  DWS Rules

Need help? Email Drinking Water Services for assistance.Staff/Partner Login