OHA Drinking Water Services
Contact Report Details |
|||
PWS ID: | OR41 90556 | ||
PWS Name: | TRIANGLE LAKE HIGH/ELEM SD 90 | ||
Who Was Contacted and Phone: | Jeff Richardson (541) 925-3262 ext. 124 | ||
Contact Date: | 09/10/2008 | ||
Contacted By: | PARRY, BETSY (REGION 2) | ||
Contact Method/Location: | Field | ||
Assistance Type: | SURVEY/DEFICIENCY FOLLOW-UP | ||
Reasons: | Lead or Copper Operations |
||
Details: | SUMMARY: checked their pH meter as follow up to WSS DETAILS: During the WSS survey July 2, we found that our agency pH meter was reading a bit lower than Jeffs. His corrosion control program requires that the waters pH remain at 7.2 or higher. Jeff has replaced the battery and calibrated his meter, and we tested it again today. I still got 7.2 on our agency meter-- he got 7.4. Jeffs next step is to order new calibration buffers (his are expired) or perhaps just order a new pH meter. Also, he showed me the bleach he has been using (Pure Bright) that meets NSF standard 60 (Jeff researched it on the NSF website and also placed a phone call to the manufacturer) even though the NSF logo does not appear on the label. ACTION NEEDED: Check back again after Jeff has gotten either a new pH meter or better buffers to calibrate the one he has. Added photos of his current bleach supply (bottle) to the recent survey photos on file, labeled with todays date. |