OHA Drinking Water Services
OHA Drinking Water Services
Contact Report Details

PWS ID: OR41 90416
PWS Name: GEORGIA-PACIFIC, WAUNA MILL
 
Who Was Contacted and Phone: Al Deichsel
Contact Date: 01/14/2009
Contacted By: TAYLOR, MAUREEN (CLATSOP COUNTY)
Contact Method/Location: Office
 
Assistance Type: WATER QUALITY ALERT RESPONSE
Reasons: SWTR
None
 
Details: SUMMARY: Turbity NTU Exceedance DETAILS: DWP phone duty personnel received call from water system on 1/12/09 at 10:99a.m. reporting turbidity problem on Sunday 1-13-09. Stated to have provided drinking water from alternative source during incident. DWP staff gave report to Evan Hofeld. Evan emailed CCHHS on 1-14-09 for follow up contact. 1-14-09 Call to Al, situation was as follows: 1-11-09 1:00 am to 4:00 am continuous read turbidity measured 1.0, 1.5, 2.0 NTU after pressure filters. Maximum read was 2.0 NTU then went back down to .10. During high NTU the water was diverted to sewer. Correction done. NTUs, both on continuous read out and in samples, have been within allowable range since 1-11-09 incident. Chlorine residuals maintained during incident. ACTION NEEDED: Informed Al the required Tier 2 notice for treatment technique violation. Gave him link for the template, requested copy for CCHHS. Recommendations per Evan H: 1-2 extra bacterial samples, double check chlorine residual, document NTU exceedance on monthly operating report.


More information for this water system: SDWIS ID 3926
System Info  ::  Report for Lenders  ::  Alerts  ::  Violations  ::  Compliance & Enforcement  ::  Contacts & Advisories  ::  Site Visits  ::  Public Notice
Coliform Summary  ::  Coliform Results  ::  Coliform Schedules  ::  LT2  ::  GW/GWUDI Source Details  ::  Plan Review  ::  Annual Fee
Chemical Summary  ::  Chemical Results  ::  Chemical Schedules  ::  Chemical Schedule Summary  ::  Arsenic RAA  ::  Cyanotoxins  ::  PFAS
Lead & Copper  ::  DBP Sample Sites  ::  FANLs  ::  MRDL  ::  GWR 4-Log  ::  Turbidity  ::  SWTR  ::  LRAA  ::  DW Source Protection
New! Visit our new Drinking Water Source Protection page.

Information for all water systems:
Water System Inventory  ::  Water System Surveys  ::  Outstanding Performers  ::  Treatment Plant Inspections  ::  Treatment  ::  Plan Reviews
Alerts  ::  Violations  ::  Compliance & Enforcement  ::  Deficiencies  ::  System Scores  ::  Exceedances  ::  Public Notices  ::  Service Lines
Water Advisories  ::  Contact Reports  ::  Cyanotoxins  ::  PFAS  ::  Post-wildfire VOCs  ::  Fluoride  ::  Certification List  ::  DW Source Protection

Introduction  ::  Data Search Options  ::  Water System Search  ::  DWS Home  ::  DWS Rules

Need help? Email Drinking Water Services for assistance.Staff/Partner Login