OHA Drinking Water Services
Contact Report Details |
|||
PWS ID: | OR41 00508 | ||
PWS Name: | MARCOLA WATER DISTRICT | ||
Who Was Contacted and Phone: | Tim Hanley (541) 746-1676 | ||
Contact Date: | 05/29/2009 | ||
Contacted By: | PARMENTER, AMY (REGION 2) | ||
Contact Method/Location: | Office | ||
Assistance Type: | SURVEY/DEFICIENCY FOLLOW-UP | ||
Reasons: | Lead or Copper Disinfection Byproducts |
||
Details: | SUMMARY: data management clarifications DETAILS: DPBs: Clarified which DBP Max sites correspond with which EPs. LCR: EPs D (Irish) and F (Spicer) are now seasonal from Jun-Sept and I told Tim he no longer has to submit monthly corrosion control reports during the off-season, as per Chuck Michael. The SDWIS Corrosion Control pages showed minimum pH set for EP-A, but this is an error, so Chuck Michael removed the minimum pH requirement, although the EP-A line can not be removed. SOC Waiver: I also reminded Tim that the SOC3 group is now an SOC5 group (as per a letter from Dennis Nelson), so he needs to sample adipates and pthalates every 3 years as well as the orginal three since the 9-year waiver does not cover those 5 chemicals. He did not sample adipates and pthlates in 05-07, so he needs to sample for them ASAP. Wellfield sampling: Also, I told him that the Wellfield requirements have changed and he should be sampling the EPs of the wellfields instead of the sources, which he had been doing anyway and will continue to do. ACTION NEEDED: Adipates and pthalates need to be sampled ASAP. |