OHA Drinking Water Services
Contact Report Details |
|||
PWS ID: | OR41 00302 | ||
PWS Name: | SOUTH COAST WATER COMPANY | ||
Who Was Contacted and Phone: | Casey Lyon, Fred Kalish (541) 726-2587 | ||
Contact Date: | 11/23/2009 | ||
Contacted By: | POTTS, JOHN (DWP) | ||
Contact Method/Location: | Field | ||
Assistance Type: | CIRCUIT RIDER ASSISTANCE | ||
Reasons: | N/A N/A |
||
Details: | SUMMARY: Tracer Study Preliminary Visit DETAILS: The Water District has installed a new 60 gpm Westech Altapac Membrane WTP. The new plant went on line in December 2008 and DWP has required a tracer study be conducted to complete the plan review process. I met with Casey Lyon and Fred Kalish to discuss the CT study procedure that is planned for the District. I met with Dan Reitz in October to conduct a preliminary inspection of the system to verify sampling points, flow records. WTP operation, etc. The distribution pump system has a maximum flow of 60 gpm-- therefore the study will be conducted at that low creating a demand on the system through an open blow off or hydrant. The study will be conducted after the storage tank plumbing modification is complete. ACTION NEEDED: Conduct CT Study. |