PWS Name: PGE BEAVER GENERATING STATION
 
Who Was Contacted and Phone: Bob Reller (503) 728-7204
Contact Date: 07/01/2011
Contacted By: NUSRALA, JAMES (REGION 1)
Contact Method/Location: Office
 
Assistance Type: BOIL WATER
Reasons: SWTR
N/A
 
Details: SUMMARY: Disinfection interruption 6/29/11 DETAILS: Bob indicated no chlorine residual at the entry point measured 1159pm on 6/29 as chlorine pump failed, potable system shut off at that time. Given that CTs last met at 12:12 am on 6/29 at the entry point, and no continuous data and no alarms, roughly 24 hours could have passed, where undisinfected water sent to system. Bob estimates that over that time, up to 19,500 gallons could have been sent to users. Following BMP, disinfection and CTs re-established at 1:30 pm on 6/30, and potable system back on. At 5 pm on 6/30, I required a boil water notice, as undisinfected water sent to system. Bob posted notice throughout plant on 6/30 in evening. System flushed out roughly 45,000 gallons of water in system at 7p on 6/30 to move any bad water out. Cl2 residuals up to 1.0 - 1.5 mg/L by 5:30 am on 7/1/11. 2 bacti samples taken at entry point to system at 8:15 am 7/1. ACTION NEEDED: I requested Bob to continue to measure cl2 residual in system. Gave Bob OERS number to call manager when bact results come back on 7/2 to consider lifting boil water notice. Bob to obtain additional sample bottles in case results are positive and system needs to repeat flushing, restoring residuals and taking coliform samples again. System will consult with DWP after coliform results from lab returned. System will send copy of boil water notice to DWP. System continuing to send treated, disinfected water through hydropneumatic tank to system and up to tower. Tower floats on system. DWP and Columbia County to provide support to PGE Beaver. I referenced BMP for disinfection interruptions on web site to Bob.


More information for this water system: SDWIS ID 4162
System Info  ::  Report for Lenders  ::  Alerts  ::  Violations  ::  Compliance & Enforcement  ::  Contacts & Advisories  ::  Site Visits  ::  Public Notice
Coliform Summary  ::  Coliform Results  ::  Coliform Schedules  ::  LT2  ::  GW/GWUDI Source Details  ::  Plan Review  ::  Annual Fee
Chemical Summary  ::  Chemical Results  ::  Chemical Schedules  ::  Chemical Schedule Summary  ::  Arsenic RAA  ::  Cyanotoxins  ::  PFAS
Lead & Copper  ::  DBP Sample Sites  ::  FANLs  ::  MRDL  ::  GWR 4-Log  ::  Turbidity  ::  SWTR  ::  LRAA  ::  DW Source Protection
New! Visit our new Drinking Water Source Protection page.

Information for all water systems:
Water System Inventory  ::  Water System Surveys  ::  Outstanding Performers  ::  Treatment Plant Inspections  ::  Treatment  ::  Plan Reviews
Alerts  ::  Violations  ::  Compliance & Enforcement  ::  Deficiencies  ::  System Scores  ::  Exceedances  ::  Public Notices  ::  Service Lines
Water Advisories  ::  Contact Reports  ::  Cyanotoxins  ::  PFAS  ::  Post-wildfire VOCs  ::  Fluoride  ::  Certification List  ::  DW Source Protection

Introduction  ::  Data Search Options  ::  Water System Search  ::  DWS Home  ::  DWS Rules

Need help? Email Drinking Water Services for assistance.Staff/Partner Login