OHA Drinking Water Services
OHA Drinking Water Services
Contact Report Details

PWS ID: OR41 94157
PWS Name: HAMLET QUICK-STOP
 
Who Was Contacted and Phone: Ludek Winkler (503) 738-0302
Contact Date: 07/27/2011
Contacted By: HOFELD, EVAN (REGION 1)
Contact Method/Location: Office
 
Assistance Type: BOIL WATER
Reasons: SWTR
Operations
 
Details: SUMMARY: Follow-up to 7/26/11 site visit and boil water advisory DETAILS: I contacted HARMSCO (800-327-3248) at 6:45 AM and asked about the significance of the retaining nut and the representative said that it keeps the cartridge in place so that it does not get damaged when pressurized. It also keeps filtered water from co-mingling with unfiltered water. I contacted Ludek that morning (7/27) at around 7:00 AM and instructed him to find the missing part and make sure it was in place. I also told him that he should not use the water for food prep, drinking, or dish washing until it was in place, the system flushed, and back on-line. I asked Ludek if the UV lamp was still working and he said it was. I sent an e-mail to Lukek clarifying the requirements and cc’d Kent, James, and Kari. A bacteriological sample taken by Alexin Analytical personnel at Hamlet Quick-Stop at 9:40 am on July 27, 2011. The results (obtained 8/2/11) showed an absence of total coliform bacteria. The sample location simply indicated “store”. ACTION NEEDED: System to initiate a boil water advisory, replace cartridge retainer nut, flush system, and take a coliform sample. System to remain on boil water advisory until results indicate an absence of bacteria.


More information for this water system: SDWIS ID 2198
System Info  ::  Report for Lenders  ::  Alerts  ::  Violations  ::  Compliance & Enforcement  ::  Contacts & Advisories  ::  Site Visits  ::  Public Notice
Coliform Summary  ::  Coliform Results  ::  Coliform Schedules  ::  LT2  ::  GW/GWUDI Source Details  ::  Plan Review  ::  Annual Fee
Chemical Summary  ::  Chemical Results  ::  Chemical Schedules  ::  Chemical Schedule Summary  ::  Arsenic RAA  ::  Cyanotoxins  ::  PFAS
Lead & Copper  ::  DBP Sample Sites  ::  FANLs  ::  MRDL  ::  GWR 4-Log  ::  Turbidity  ::  SWTR  ::  LRAA  ::  DW Source Protection
New! Visit our new Drinking Water Source Protection page.

Information for all water systems:
Water System Inventory  ::  Water System Surveys  ::  Outstanding Performers  ::  Treatment Plant Inspections  ::  Treatment  ::  Plan Reviews
Alerts  ::  Violations  ::  Compliance & Enforcement  ::  Deficiencies  ::  System Scores  ::  Exceedances  ::  Public Notices  ::  Service Lines
Water Advisories  ::  Contact Reports  ::  Cyanotoxins  ::  PFAS  ::  Post-wildfire VOCs  ::  Fluoride  ::  Certification List  ::  DW Source Protection

Introduction  ::  Data Search Options  ::  Water System Search  ::  DWS Home  ::  DWS Rules

Need help? Email Drinking Water Services for assistance.Staff/Partner Login