OHA Drinking Water Services
Contact Report Details |
|||
PWS ID: | OR41 05364 | ||
PWS Name: | MT TERRACE MHP | ||
Who Was Contacted and Phone: | Rob Henry | ||
Contact Date: | 04/17/2012 | ||
Contacted By: | MACPHERSON, JAMES (REGION 2) | ||
Contact Method/Location: | Office | ||
Assistance Type: | PLAN REVIEW | ||
Reasons: | SWTR Operations |
||
Details: | SUMMARY: Tracer study proposal DETAILS: Physical configuration of system will result in pulsed draw from the wells due to a booster pump that is almost an order of magnitude more powerful than the well pumps. There is a 900 gallon reservoir floating on the system that will likely drive the periodicity of the booster pump. This is OK as it is how the system operates. A key data acquisition will be flow rate during the tracer study. Flow needs to be more than 27 gpm, and optimally between 36 and 46 gpm. ACTION NEEDED: none |