OHA Drinking Water Services
Contact Report Details |
|||
PWS ID: | OR41 94157 | ||
PWS Name: | HAMLET QUICK-STOP | ||
Who Was Contacted and Phone: | Ludek Winkler (503) 738-0302 | ||
Contact Date: | 06/15/2012 | ||
Contacted By: | HOFELD, EVAN (REGION 1) | ||
Contact Method/Location: | Field | ||
Assistance Type: | OTHER REGULATORY - REGULATORY ASSISTANCE | ||
Reasons: | SWTR Operations |
||
Details: | SUMMARY: Stopped by to check in on operations and check turbidity DETAILS: I stopped in to check the filter effluent turbidity and see how things were going. The turbidity was measured to be 0.5 NTU and the chlorine residual was holding steady at around 0.7 - 0.8 mg/l. I explained that the turbidity should always be less than 1 NTU and to call our office if results were ever above that level. I let him know that he had reported 5 NTU, but he thought that he had not recorded the results accurately. ACTION NEEDED: Keep monitoring chlorine residuals and turbidity and keep DWP apprised of high turbidity or low chlorine residuals. |