OHA Drinking Water Services
Contact Report Details |
|||
PWS ID: | OR41 00463 | ||
PWS Name: | LAKESIDE WATER DISTRICT | ||
Who Was Contacted and Phone: | Marty Ball (541) 260-7794 | ||
Contact Date: | 08/03/2012 | ||
Contacted By: | MACPHERSON, JAMES (REGION 2) | ||
Contact Method/Location: | Office | ||
Assistance Type: | OTHER REGULATORY - REGULATORY ASSISTANCE | ||
Reasons: | SWTR None |
||
Details: | SUMMARY: Required CT values from look-up tables DETAILS: When using the look-up tables for required CT, round pH values UP and temperature values DOWN. Currently the closest value is being used. If pH is 7.1, then the table with pH of 7.5 should be used. If the temperature is 11 degrees C, the table for 10 degrees C should be used. There is a regression equation available that will calculate the required CT very accurately without need for rounding. Past efforts to email this to Lakeside have not been successful. ACTION NEEDED: none |