OHA Drinking Water Services
Contact Report Details |
|||
PWS ID: | OR41 00012 | ||
PWS Name: | ALBANY, CITY OF | ||
Who Was Contacted and Phone: | Mark Yeager | ||
Contact Date: | 08/23/2012 | ||
Contacted By: | MACPHERSON, JAMES (REGION 2) | ||
Contact Method/Location: | Field | ||
Assistance Type: | OTHER REGULATORY - REGULATORY ASSISTANCE | ||
Reasons: | SWTR None |
||
Details: | SUMMARY: LT2 compliance options DETAILS: While maintaining compliance and protection of public health, is there something that can be done in conjunction with upcoming system upgrades that would provide 0.5-log treatment credit for LT2 compliance? Discussed how Albany could attain credit for maintaining a CFE value below 0.15. Is the influent pipe to the Maple Street reservoir a valid CFE location? No, because the original clearwell provides storage before this point. Watershed protection not likely practical and there is no assurance a plan would be accepted. Membranes or UV are expensive. ACTION NEEDED: What could be done to obtain the CFE credit given the current plant configuration? |