OHA Drinking Water Services
Contact Report Details |
|||
PWS ID: | OR41 93997 | ||
PWS Name: | OREGON INSTITUTE OF TECHNOLOGY | ||
Who Was Contacted and Phone: | Scott Keiffer (541) 281-3447 | ||
Contact Date: | 02/04/2013 | ||
Contacted By: | PARRY, BETSY (REGION 2) | ||
Contact Method/Location: | Office | ||
Assistance Type: | OTHER REGULATORY - REGULATORY ASSISTANCE | ||
Reasons: | Arsenic None |
||
Details: | SUMMARY: Arsenic exceedance resolved at the Residence Hall DETAILS: After learning of the MCL violation on 12/28/12, OIT found the quickest turn-around time for a vendor, and replaced the media in this arsenic treatment unit at the campus Residence Hall on 1/16/13. They took a new arsenic sample in this building on 1/22/2013, and the result was "no detection." This lab result was received today. The system plans to update the public notice at this building, reflecting the results of their actions and their return to compliance with the drinking water standards. The system must sample quarterly for arsenic at this location for a year. ACTION NEEDED: We cannot change arsenic sampling schedules in the database for specific locations, so must keep track of these 4 required quarterly samples separately. |