PWS Name: WICKIUP WATER DISTRICT
 
Who Was Contacted and Phone: Dan Waterbury (503) 791-5751
Contact Date: 01/28/2014
Contacted By: HOFELD, EVAN (REGION 1)
Contact Method/Location: Office
 
Assistance Type: WATER QUALITY ALERT RESPONSE
Reasons: SOCs
SOC
 
Details: SUMMARY: Diquate Confirmation Sample DETAILS: I received an alert on 10/23/13 for a detection of Diquat at 0.0004 mg/l from a sample taken at EP-B (Little Cr Rapid Rate Plant) on 9/18/13. I advised that a confirmation sample be taken as soon as possible to determine if quarterly monitoring is needed. A confirmation sample taken 12/4/13 from both the Little Creek source (SRC-BA) and the the entry point (EP-B) were both non-detect for Diquat. The average of the two entry point results is 0.0002 mg/l, which is less than the detection limit of 0.0004 mg/l for Diquat. I spoke to Dan Waterbury on 1/28/14 and notified him that due to the non-detect confirmation samples, quarterly monitoring for Diquat was no longer needed, but that quarterly monitoring for Xylenes and Ethylbenzene is still needed for 1st and 2nd quarter 2014 (see contact report dated 11/04/13 for more info on VOCs). ACTION NEEDED: Quarterly monitoring for Diquat is no longer needed due to non-detect confirmation sampling completed 12/4/13. Quarterly monitoring for Xylenes and Ethylbenzene is still needed for 1st and 2nd quarter 2014 (see contact report dated 11/04/13 for more info on VOCs).
 
Associated Alerts: CHEM6022 - 10/23/2013 - DIQUAT



More information for this water system: SDWIS ID 3875
System Info  ::  Report for Lenders  ::  Alerts  ::  Violations  ::  Compliance & Enforcement  ::  Contacts & Advisories  ::  Site Visits  ::  Public Notice
Coliform Summary  ::  Coliform Results  ::  Coliform Schedules  ::  LT2  ::  GW/GWUDI Source Details  ::  Plan Review  ::  Annual Fee
Chemical Summary  ::  Chemical Results  ::  Chemical Schedules  ::  Chemical Schedule Summary  ::  Arsenic RAA  ::  Cyanotoxins  ::  PFAS
Lead & Copper  ::  DBP Sample Sites  ::  FANLs  ::  MRDL  ::  GWR 4-Log  ::  Turbidity  ::  SWTR  ::  LRAA  ::  DW Source Protection
New! Visit our new Drinking Water Source Protection page.

Information for all water systems:
Water System Inventory  ::  Water System Surveys  ::  Outstanding Performers  ::  Treatment Plant Inspections  ::  Treatment  ::  Plan Reviews
Alerts  ::  Violations  ::  Compliance & Enforcement  ::  Deficiencies  ::  System Scores  ::  Exceedances  ::  Public Notices  ::  Service Lines
Water Advisories  ::  Contact Reports  ::  Cyanotoxins  ::  PFAS  ::  Post-wildfire VOCs  ::  Fluoride  ::  Certification List  ::  DW Source Protection

Introduction  ::  Data Search Options  ::  Water System Search  ::  DWS Home  ::  DWS Rules

Need help? Email Drinking Water Services for assistance.Staff/Partner Login