OHA Drinking Water Services
OHA Drinking Water Services
Contact Report Details

PWS ID: OR41 00672
PWS Name: POWERS, CITY OF
 
Who Was Contacted and Phone: Harry Pierson (541) 404-9216
Contact Date: 04/25/2016
Contacted By: SALIS, KARI (DWP)
Contact Method/Location: Office
 
Assistance Type: OTHER REGULATORY - REGULATORY ASSISTANCE
Reasons: Operations
SWTR
 
Details: SUMMARY: WTP operations DETAILS: Harry called phone duty to ask if the requirement for filter backwash was 72 hours of filter run time only, or 72 hours on the clock. He said they run their plant for 8-10 hours each day and it is off the rest of the time. I said it was not a requirement, but a recommendation to start a filter run on a clean (backwashed) filter. He thought that seemed reasonable and they have made changes to their backwash pond so that this can happen easier. He also asked about peak hourly flow calculations. He said sometimes (maybe twice a month) the flow is so low or for just a few minutes at a time, that it is difficult to calculate the peak hourly flow. He said that during these times, they would like to estimate and record the peak hourly flow to be 30 gpm. Their tracer study was done at a much higher flow and they have plenty of contact time. I said this seemed reasonable as long as they document what they are doing in a procedure so everyone understands what to do and what it means. ACTION NEEDED: None necessarily, but state contact can follow up if anything I said needs clarification. Also he said he is new, so not sure if he is the new contact or DRC.


More information for this water system: SDWIS ID 3901
System Info  ::  Report for Lenders  ::  Alerts  ::  Violations  ::  Compliance & Enforcement  ::  Contacts & Advisories  ::  Site Visits  ::  Public Notice
Coliform Summary  ::  Coliform Results  ::  Coliform Schedules  ::  LT2  ::  GW/GWUDI Source Details  ::  Plan Review  ::  Annual Fee
Chemical Summary  ::  Chemical Results  ::  Chemical Schedules  ::  Chemical Schedule Summary  ::  Arsenic RAA  ::  Cyanotoxins  ::  PFAS
Lead & Copper  ::  DBP Sample Sites  ::  FANLs  ::  MRDL  ::  GWR 4-Log  ::  Turbidity  ::  SWTR  ::  LRAA  ::  DW Source Protection
New! Visit our new Drinking Water Source Protection page.

Information for all water systems:
Water System Inventory  ::  Water System Surveys  ::  Outstanding Performers  ::  Treatment Plant Inspections  ::  Treatment  ::  Plan Reviews
Alerts  ::  Violations  ::  Compliance & Enforcement  ::  Deficiencies  ::  System Scores  ::  Exceedances  ::  Public Notices  ::  Service Lines
Water Advisories  ::  Contact Reports  ::  Cyanotoxins  ::  PFAS  ::  Post-wildfire VOCs  ::  Fluoride  ::  Certification List  ::  DW Source Protection

Introduction  ::  Data Search Options  ::  Water System Search  ::  DWS Home  ::  DWS Rules

Need help? Email Drinking Water Services for assistance.Staff/Partner Login