OHA Drinking Water Services
Contact Report Details |
|||
PWS ID: | OR41 90556 | ||
PWS Name: | TRIANGLE LAKE HIGH/ELEM SD 90 | ||
Who Was Contacted and Phone: | ALG lab report | ||
Contact Date: | 07/13/2016 | ||
Contacted By: | MACPHERSON, JAMES (REGION 2) | ||
Contact Method/Location: | Office | ||
Assistance Type: | WATER QUALITY ALERT RESPONSE | ||
Reasons: | Lead or Copper Operations |
||
Details: | SUMMARY: pH minimum is not met DETAILS: Lab staff measured pH in field at entry point, cafeteria, and gym. Readings were 5.97, 6.20, and 5.98, respectively, and confirmed by lab values. Thus, corrosion control treatment is not being operated correctly. This puts into question whether past readings from PWS are accurate, and thus a pH of 7.2 may in fact be adequate for optimal corrosion control. ACTION NEEDED: Lane County to query operator about pH measurements accuracy. | ||
Associated Alerts: | n/a - - |