OHA Drinking Water Services
OHA Drinking Water Services
Contact Report Details

PWS ID: OR41 01449
PWS Name: MARSHLAND WATER ASSOCIATION
 
Who Was Contacted and Phone: Bob Bedell (503) 728-3144
Contact Date: 08/29/2016
Contacted By: NUSRALA, JAMES (REGION 1)
Contact Method/Location: Office
 
Assistance Type: WATER QUALITY ALERT RESPONSE
Reasons: Disinfection Byproducts
N/A
 
Details: SUMMARY: Follow up on HAA5 - DBP level above the MCL DETAILS: After leaving a couple of voice messages, I emailed Bob after the Aug 19th, 0.0642 mg/L detection of haloacetic acids-HAA5, which is above the MCL of 0.060 mg/L. I indicated that compliance with the MCL is based on a running annual average of 4 quarters, and since the average is below 0.060 mg/L, there is no violation of the MCL at this time. Additionally, the Operational Evaluation Level of 0.060, based on the past 3 quarterly values, has not been exceeded, no report needed at this time. Therefore, system to stay on quarterly DBP sampling. ACTION NEEDED: System to stay on quarterly DBP sampling for both TTHM and HAA5 during November, February, May, August. DWS to provide support to assist Association in managing DBP levels. 9/7/16 update: I reached Bob and he indicated the recirculation pump that has been used to simulate flushing and move water through distribution system and tank had a pump that needed to be replaced during the August period. Pump fixed and system recirculating water at this point.
 
Associated Alerts: CHEM7253 - 08/19/2016 - TOTAL HALOACETIC ACIDS (HAA5)



More information for this water system: SDWIS ID 4016
System Info  ::  Report for Lenders  ::  Alerts  ::  Violations  ::  Compliance & Enforcement  ::  Contacts & Advisories  ::  Site Visits  ::  Public Notice
Coliform Summary  ::  Coliform Results  ::  Coliform Schedules  ::  LT2  ::  GW/GWUDI Source Details  ::  Plan Review  ::  Annual Fee
Chemical Summary  ::  Chemical Results  ::  Chemical Schedules  ::  Chemical Schedule Summary  ::  Arsenic RAA  ::  Cyanotoxins  ::  PFAS
Lead & Copper  ::  DBP Sample Sites  ::  FANLs  ::  MRDL  ::  GWR 4-Log  ::  Turbidity  ::  SWTR  ::  LRAA  ::  DW Source Protection
New! Visit our new Drinking Water Source Protection page.

Information for all water systems:
Water System Inventory  ::  Water System Surveys  ::  Outstanding Performers  ::  Treatment Plant Inspections  ::  Treatment  ::  Plan Reviews
Alerts  ::  Violations  ::  Compliance & Enforcement  ::  Deficiencies  ::  System Scores  ::  Exceedances  ::  Public Notices  ::  Service Lines
Water Advisories  ::  Contact Reports  ::  Cyanotoxins  ::  PFAS  ::  Post-wildfire VOCs  ::  Fluoride  ::  Certification List  ::  DW Source Protection

Introduction  ::  Data Search Options  ::  Water System Search  ::  DWS Home  ::  DWS Rules

Need help? Email Drinking Water Services for assistance.Staff/Partner Login