OHA Drinking Water Services
OHA Drinking Water Services
Contact Report Details

PWS ID: OR41 05776
PWS Name: NATL CLONAL GERMPLASM REPOSIT (NCGR)
 
Who Was Contacted and Phone: Jeffrey Strang
Contact Date: 01/30/2017
Contacted By: FREY, GRETA (LINN COUNTY)
Contact Method/Location: Office
 
Assistance Type: WATER QUALITY ALERT RESPONSE
Reasons: Coliform
N/A
 
Details: SUMMARY: E.coli at the Source DETAILS: A positive E.Coli sample was taken at the well on 1/27/2017. A level 1 coliform investigation was conducted and completed last week. The positive E.Coli sample was taken on 1/27, the source sample was taken after the repeats because there was an issue with the sample tap. The water system shocked the well after the level 1, so the 24 hours to take the 5 confirmation source samples will not apply to this system.They will take their 3 routine samples on 2/3/17 and they will take the 5 confirmation source samples when they can demonstrate their source does not have chlorine residual.Note: The water at the NCGR lab is not used for drinking, it is used for handwashing only. ACTION NEEDED: Remain on a boil notice until samples are negative to total coliform or E.Coli.
 
Associated Alerts: COLI16523 - 01/30/2017 - COLIFORM (TCR) , E. COLI

COLI16523 - 01/30/2017 - COLIFORM (TCR) , E. COLI



More information for this water system: SDWIS ID 553
System Info  ::  Report for Lenders  ::  Alerts  ::  Violations  ::  Compliance & Enforcement  ::  Contacts & Advisories  ::  Site Visits  ::  Public Notice
Coliform Summary  ::  Coliform Results  ::  Coliform Schedules  ::  LT2  ::  GW/GWUDI Source Details  ::  Plan Review  ::  Annual Fee
Chemical Summary  ::  Chemical Results  ::  Chemical Schedules  ::  Chemical Schedule Summary  ::  Arsenic RAA  ::  Cyanotoxins  ::  PFAS
Lead & Copper  ::  DBP Sample Sites  ::  FANLs  ::  MRDL  ::  GWR 4-Log  ::  Turbidity  ::  SWTR  ::  LRAA
Corrosion Control has moved to the Lead & Copper page.

Information for all water systems:
Water System Inventory  ::  Water System Surveys  ::  Outstanding Performers  ::  Treatment Plant Inspections  ::  Treatment  ::  Plan Reviews
Alerts  ::  Violations  ::  Compliance & Enforcement  ::  Deficiencies  ::  System Scores  ::  Exceedances  ::  Public Notices  ::  Service Lines
Water Advisories  ::  Contact Reports  ::  Cyanotoxins  ::  PFAS  ::  Post-wildfire VOCs  ::  Fluoride  ::  Certification List

Introduction  ::  Data Search Options  ::  Water System Search  ::  DWS Home  ::  DWS Rules

Need help? Email Drinking Water Services for assistance.Staff/Partner Login