OHA Drinking Water Services
Contact Report Details |
|||
PWS ID: | OR41 91692 | ||
PWS Name: | SWEET HOME CHARTER SCHOOL | ||
Who Was Contacted and Phone: | TAVIA THORNTON (541) 637-1833 | ||
Contact Date: | 10/18/2016 | ||
Contacted By: | HENRY, ROBERT (DWP) | ||
Contact Method/Location: | Office | ||
Assistance Type: | CIRCUIT RIDER ASSISTANCE | ||
Reasons: | N/A N/A |
||
Details: | SUMMARY: LEAD ISSUES DETAILS: The Sweet Home Charter School has a groundwater system that provides drinking water to the students and faculty. There is a single well located just to the west of the school. The Sweet Home Charter School had been on the 3 Year sample interval for Lead and Copper. In the tests from September 2016, the Action Level for Lead was exceeded, with a sampled result of 0.0170 mg/L at a classroom sink (Action Level is 0.0155 mg/L). An adjacent classroom sink had a result of 0.0146 mg/L, just below the Action Level. The water system contacted the Circuit Rider to provide assistance with parameter testing for a potential corrosion control system. Previously communicated with school principal regarding operational issues, as well as sampling techniques. Composed memo detailing parameters to be tested. Corresponded with principal regarding question about sampling. ACTION NEEDED: Assist with interpretation of the corrosion control parameters. |