Most Recent Water System Survey | |||||||||||||||||||||||||||||||||
Survey Date: | Mar 17, 2022 | ||||||||||||||||||||||||||||||||
Notification Date: | Apr 06, 2022 (20 days) | ||||||||||||||||||||||||||||||||
Regulating Agency: | DWS (REGION 2) | ||||||||||||||||||||||||||||||||
Survey Frequency: | 5 YR - Visit the Water System Surveys page to see the list of surveys due each year. | ||||||||||||||||||||||||||||||||
Deficiencies: |
Bold text indicates that resolving this deficiency is a top priority. * Corrective Action Plan has been submitted for this deficiency. |
Water System Site Visit History | ||||||||||||||||||||||||||||||||||||||||||
Reason | Visit Date | Frequency | Next Due | Notification Date (Days after survey) |
Responsible Agency |
Comments and Deficiencies |
||||||||||||||||||||||||||||||||||||
---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
Sanitary Survey, Finished (SNSV) | 03/17/2022 | 5 YR | * | 04/06/2022 (20) | REGION 2 | Show details | ||||||||||||||||||||||||||||||||||||
Water Treatment Plant Site Visit (TRTP) | 03/17/2022 | 1 YR | 03/17/2023 | 04/06/2022 (20) | REGION 2 | No details | ||||||||||||||||||||||||||||||||||||
Sanitary Survey, Finished (SNSV) | 07/21/2015 | 3 YR | * | 08/06/2015 (16) | REGION 2 | Show details | ||||||||||||||||||||||||||||||||||||
Water Treatment Plant Site Visit (TRTP) | 07/21/2015 | 3 YR | 07/21/2018 | 08/06/2015 (16) | REGION 2 | No details | ||||||||||||||||||||||||||||||||||||
Sanitary Survey, Finished (SNSV) | 10/07/2010 | 3 YR | * | 12/15/2010 (69) | COOS COUNTY | Hide details | ||||||||||||||||||||||||||||||||||||
Comments: Treatment: -Incorrect location for compliance turbidity monitoring. -Turbidity standards not met. -Non-NSF approved chemicals being used. -No screened vents for both sand filter's effluent. Finished Water Storage: -Roof, side walls and access hatch not watertight. -Hatch not locked or adequately secured. -Tank overflow pipe lacks screen. Management & Operations: -No coliform sampling plan. -No operations & maintenance manual.
Deficiency dates were not tracked prior to 1/1/2014. | ||||||||||||||||||||||||||||||||||||||||||
Sanitary Survey, Finished (SNSV) | 11/30/2005 | 5 YR | * | 02/07/2006 (69) | COOS COUNTY | No details | ||||||||||||||||||||||||||||||||||||
Sanitary Survey, Finished (SNSV) | 04/09/1999 | 5 YR | * | COOS COUNTY | Show details | |||||||||||||||||||||||||||||||||||||