OHA Drinking Water Services
Contact Report Details |
|||
PWS ID: | OR41 00521 | ||
PWS Name: | VINCENT WATER COMPANY | ||
Who Was Contacted and Phone: | Frank Douglas | ||
Contact Date: | 08/03/2006 | ||
Contacted By: | BURNETT, GARY (DWP) | ||
Contact Method/Location: | Field | ||
Assistance Type: | WATER QUALITY ALERT RESPONSE | ||
Reasons: | Coliform N/A |
||
Details: | SUMMARY: Sample taken 8/01 E.coli positive. DETAILS: A sample taken on 8/01 was total coliform positive. Burnett contacted Frank Douglas, Larry Lawrence, and Marvin Hare on 8/02. Repeat samples were taken and then the chlorinator was activated on the evening of 8/02. On 8/03 Burnett inspected the system and measured a chlorine residual of 0.2 mg/l in the distribution system. ACTION NEEDED: 8/04 - All repeat samples were negative so there is no TCR violation. 5 Routine samples required in September. |