OHA Drinking Water Services
Contact Report Details |
|||
PWS ID: | OR41 00635 | ||
PWS Name: | SUNRISE WATER AUTHORITY | ||
Who Was Contacted and Phone: | Tim Jannsen (503) 761-0220 | ||
Contact Date: | 08/23/2013 | ||
Contacted By: | FARRELLY, PETER (DWP) | ||
Contact Method/Location: | Office | ||
Assistance Type: | WATER QUALITY ALERT RESPONSE | ||
Reasons: | Coliform N/A |
||
Details: | SUMMARY: TC+ repeat at same sample tap. DETAILS: While this second TC+ at the original sample station is enough evidence to invalidate the sample tap and move on, Sunrise did a second round of repeats as well as re-examined their sampling protocols & stations. In so doing, they determined a possible culprit in their summer mystery TC+s. In a sample station there are 2 lines - a sample line and a drain line for winterizing the station. Their drain lines have perhaps never been flushed. They opened both lines for all their second-round-repeats. All these results came back TC-. ACTION NEEDED: Sunrise WA will likely change their coliform sampling protocol to flush both lines either every time or at least more frequently. |
||
Associated Alerts: | COLI11989 - 08/22/2013 - COLIFORM (TCR) |