Deficiencies: |
Category |
Deficiency |
Due Date |
Resolved Date |
Cross Connection |
Annual summary report not issued (CWS) | Aug 24, 2021 |
Jun 30, 2021
|
Surface Water Treatment |
For conventional or direct filtration: No alarm or plant shut off for high turbidity | Aug 24, 2021 |
Aug 01, 2021
|
Surface Water Treatment |
Turbidimeters not calibrated per manufacturer or at least quarterly | Sep 30, 2021 * |
Sep 30, 2021
|
Surface Water Treatment |
For conventional or direct filtration: Turbidity profile not conducted on individual filters at least quarterly | Sep 30, 2021 * |
Sep 30, 2021
|
Disinfection |
pH, temperature, and chlorine residual not measured daily at first user | Nov 30, 2021 * |
Nov 30, 2021
|
* Corrective Action Plan has been submitted for this deficiency.
|